Permit Number: T14CM00045
Parcel: 12801005H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T14CM00045
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/18/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. PREVIOUS COMMENT 1; SHEET A00.00; CODE SYNOPSIS: DID NOT UPDATE THE ICC/ANSI TO THE 2009 EDITION.
2. PREVIOUS COMMENT 2; SHEET A00.10: DID NOT REVISE THE LETTERING SIZE FOR THE BUILDING DIMENSIONS, TRAVEL DISTANCES, AND EGRESS NOTES.
3. SHEET A08.08; PLAN SECTION A: A NOTE FOR PKF/6 ('CUT TO SIZE') COVERS A SECTION CUT. CLEAR UP THE VERBIAGE.
4. PREVIOUS COMMENT; SHEET A10.10: DID NOT REVISE THE LETTERING SIZE FOR THE SECTION INDICATORS.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
02/27/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
02/27/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed
02/27/2014 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/06/2014 SHANAE POWELL OUT TO CUSTOMER Completed
03/06/2014 CPIERCE1 REJECT SHELF Completed