Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T14CM00045
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/18/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. PREVIOUS COMMENT 1; SHEET A00.00; CODE SYNOPSIS: DID NOT UPDATE THE ICC/ANSI TO THE 2009 EDITION. 2. PREVIOUS COMMENT 2; SHEET A00.10: DID NOT REVISE THE LETTERING SIZE FOR THE BUILDING DIMENSIONS, TRAVEL DISTANCES, AND EGRESS NOTES. 3. SHEET A08.08; PLAN SECTION A: A NOTE FOR PKF/6 ('CUT TO SIZE') COVERS A SECTION CUT. CLEAR UP THE VERBIAGE. 4. PREVIOUS COMMENT; SHEET A10.10: DID NOT REVISE THE LETTERING SIZE FOR THE SECTION INDICATORS. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 02/27/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/27/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 02/27/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/06/2014 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 03/06/2014 | CPIERCE1 | REJECT SHELF | Completed |