Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T14CM00045
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2014 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 01/09/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A00.00; CODE SYNOPSIS: REVISE THE ICC/ANSI A117.1 TO THE 2009 EDITION. 2. SHEET A00.00: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE BUILDING DIMENSIONS, TRAVEL DISTANCES, AND EGRESS NOTES. 3. SHEET A00.10; ACCESSIBILITY PLAN: REVISE THE "1/3 BUILDING DIAGONAL" FROM 58" . 4. SHEET A01.01: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PLAN ELEVATION INDICATORS. 5. SHEET A01.01; DEMOLITION PLAN: NOTES 19 AND 26 WERE NOT LOCATED ON THE PLAN. VERIFY. PROVIDE A NOTE THAT NOT ALL KEYNOTES LISTED ARE REFERENCED ON THIS SHEET. 6. SHEET A01.02: PROVIDE A NOTE THAT NOT ALL KEYNOTES LISTED ARE REFERENCED ON THIS SHEET. 7. SHEETS A01.11 AND A01.12: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PLAN/ELEVATION SECTION INDICATORS. 8. SHEETS A02.01, A02.02, AND A02.10: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED PLAN INDICATORS. 9. SHEETS A02.01, A02.02, AND A02.10: PROVIDE A NOTE THAT NOT ALL KEYNOTES LISTED ARE REFERENCED ON THIS SHEET. 10. SHEETS A03.01 AND A03.02: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED PLAN INDICATORS. 11. SHEETS A03.01 AND A03.02: PROVIDE A NOTE THAT NOT ALL KEYNOTES LISTED ARE REFERENCED ON THIS SHEET. 12. SHEETS A04.01 AND A04.02: PROVIDE A NOTE THAT NOT ALL KEYNOTES LISTED ARE REFERENCED ON THIS SHEET. 13. SHEETS A05.01 AND A05.02: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ELEVATION INDICATORS. 14. SHEETS A05.01 AND A05.02: PROVIDE A NOTE THAT NOT ALL KEYNOTES LISTED ARE REFERENCED ON THIS SHEET. 15. SHEETS A06.01 AND A06.02: PROVIDE A NOTE THAT NOT ALL KEYNOTES LISTED ARE REFERENCED ON THIS SHEET. 16. SHEETS A07.01 THROUGH A07.04: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED ELEVATION INDICATORS. 17. THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED ELEVATION INDICATORS. 18. SHEETS A08.01 THROUGH A08.03: PROVIDE A NOTE THAT NOT ALL KEYNOTES LISTED ARE REFERENCED ON THIS SHEET. 19. SHEETS A08.05 THROUGH A08.08: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED PLAN/SECTION INDICATORS. 20. SHEETS A08.10 THROUGH A08.13: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED SECTION INDICATORS. 21. SHEET A08.15: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED ELEVATION/SECTION INDICATORS. 22. SHEET A08.17: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED SECTION INDICATORS. 23. SHEETS A10.01 THROUGH A10.03: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED ELEVATION/SECTION INDICATORS. 24. SHEETS A10.05 THROUGH A10.07: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED ELEVATION/SECTION INDICATORS. 25. SHEETS A10.09 THROUGH A10.10: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED ELEVATION/SECTION INDICATORS. 26. SHEETS A11.01 THROUGH A11.09: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED ELEVATION/SECTION INDICATORS. 27. ALL STRUCTURAL SHEETS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE ENLARGED ELEVATION/SECTION/PLAN INDICATORS. 28. SHEET S01.01; STRUCTURAL NOTES (A): REVISE THE BUILDING CODE TO THE 2012 EDITION AND VERIFY ALL REQUIREMENTS OF THE 2012 CODE AND CITY OF TUCSON AMENDMENTS ARE SATISFIED. 29. SHEET S01.01; STRUCTURAL NOTES (C): ARE THERE ANY HIGH STRENGTH BOLTS USED ON THIS PROJECT? VERIFY. 30. GENERAL: ARE THERE ANY STRUCTURAL CALCULATIONS ON THIS PROJECT? CALCULATIONS ARE REQUIRED FOR THE NEW WALL FRAMING AT THE SOFFITS AND THE LEDGE FRAMING. IN ADDITION, PROVIDE CALCULATIONS TO VERIFY THE EXISTING ROOF STRUCTURE IS CAPABLE OF SUPPORTING THE NEW ROOFTOP UNIT #3. 31. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/14/2014 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 01/14/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Indicate the location for water heater WH-1; it is specified on the plumbing fixture schedule but does not appear on any of the other plumbing drawings or the electrical drawings. 3. Provide the specifications and listing information for the proposed water heater, WH-2. Reference: Sections 303.2 and 501.5, IPC 2012 and Section 107.2.1, IBC 2012. 4. Provide tempered water for the lavatories and public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012 5. The design of the water heater piping (detail B/P03.01), with a shut off valve located between the water heater and the expansion tank, makes it impossible for the expansion tank to accommodate the thermal expansion of the water in the water heater, as intended by Section 607.3, IPC 2012. Note that the expansion tank is required for this installation. 6. Cleanouts shall open to allow cleaning in the direction of flow (see the floor cleanout in the horizontal drain from the break room sink on sheets P02.02 and P02.03). Reference: Section 708.5, IPC 2012. |
| 01/14/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Verify the efficiency of the electric heaters in RTU-1 and FPVAV-1. Reference: Section C403.2.3, IECC 2012. |
| 01/16/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Provide plans sealed by an Arizona Registrant. Reference: Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304. 2. Provide calculations or interior lighting power compliance certificate showing compliance with IEEC section 405.5. 3. Provide fault current calculations justifying stated available fault current at equipment. 4. Errata: PPE0.01 has RTU 1 circuited to MDP 3 |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/12/2014 | AROMERO4 | OUT TO CUSTOMER | Completed |