Permit Number: T14BU01356
Parcel: 111081410

Address:
3505 E GRANT RD

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T14BU01356
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2015 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized electrical repair submittal for COT ID# 434 at 3505 East Grant Road (T14BU01356).


Sheet 1 of 2


No comments.


Sheet 2 of 2


1. In panel schedule, load is understated; correct to reflect ballast input for four HO lamps and 125% load factor (see Load Calcs for T14BU00861).


2. In panel schedule, include timer load.


3. In West Face Sign Elevation, depict approximate location of joint where replacement EMT joins existing EMT that remains in place
12/16/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/22/2015 AROMERO4 OUT TO CUSTOMER Completed