Review Details: TANKS
Permit Number - T14BU01234
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/05/2015 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 01/16/2015 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | PREVIOUS COMMENTS WERE NOT ADDRESSED ON THE DRAWINGS: 1. SHEET A-11 (ENLARGE PLAN); KEYNOTES: NOTE 9 INDICATES PIPE BOLLARDS AT 5'-0" O.C., WHILE THE PLAN INDICATES 4'-0" TYPICAL SPACING. CLARIFY. 2. SHEET A-11 (BOLLARD DETAIL 10); SHEET A-12 (TANK PLAN 2): A NOTE ON THE PLAN AT A PIPE BOLLARD INDICATES A 36" HIGH BOLLARD, WHILE DETAIL 10 INDICATES A 3'-6" HEIGHT. CLARIFY. 3. SHEET A-12; TANK PLAN 2: PROVIDE A NORTH ARROW ON THE PLAN. 4. SHEET A-12; TANK PAD SECTION 12: PROVIDE A DIMENSION ON THE SECTION INDICATING THE CLEAR DISTANCE FROM THE TOP OF THE SLAB TO THE UPPER REBAR. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/26/2015 | CPIERCE1 | REJECT SHELF | Completed |