Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14BU01234
Parcel: 10609027F

Address:
1770 W PRINCE RD

Review Status: Completed

Review Details: TANKS

Permit Number - T14BU01234
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/05/2015 DAVID RIVERA ZONING REVIEW Approved
01/16/2015 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change PREVIOUS COMMENTS WERE NOT ADDRESSED ON THE DRAWINGS:
1. SHEET A-11 (ENLARGE PLAN); KEYNOTES: NOTE 9 INDICATES PIPE BOLLARDS AT 5'-0" O.C., WHILE THE PLAN INDICATES 4'-0" TYPICAL SPACING. CLARIFY.
2. SHEET A-11 (BOLLARD DETAIL 10); SHEET A-12 (TANK PLAN 2): A NOTE ON THE PLAN AT A PIPE BOLLARD INDICATES A 36" HIGH BOLLARD, WHILE DETAIL 10 INDICATES A 3'-6" HEIGHT. CLARIFY.
3. SHEET A-12; TANK PLAN 2: PROVIDE A NORTH ARROW ON THE PLAN.
4. SHEET A-12; TANK PAD SECTION 12: PROVIDE A DIMENSION ON THE SECTION INDICATING THE CLEAR DISTANCE FROM THE TOP OF THE SLAB TO THE UPPER REBAR.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/26/2015 CPIERCE1 REJECT SHELF Completed