Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14BU01234
Parcel: 10609027F

Address:
1770 W PRINCE RD

Review Status: Completed

Review Details: TANKS

Permit Number - T14BU01234
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2014 KEN BROUILLETTE FIRE REVIEW Approved
12/11/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
12/11/2014 DAVID RIVERA ZONING REVIEW Denied FROM: David Rivera
Principal Planner

PROJECT: TP14BU01234
1770 W Prince Road
Development Package - United Rentals

TRANSMITTAL DATE: November 28, 2014

DUE DATE: December 18, 2014

Zoning cannot approve the Fuel tank application until the Development Package site plan is approved.
12/12/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. SHEET A-11 (ENLARGE PLAN); KEYNOTES: NOTE 9 INDICATES PIPE BOLLARDS AT 5'-0" O.C., WHILE THE PLAN INDICATES 4'-0" TYPICAL SPACING. CLARIFY.
2. SHEET A-11 (BOLLARD DETAIL 10); SHEET A-12 (TANK PLAN 2): A NOTE ON THE PLAN AT A PIPE BOLLARD INDICATES A 36" HIGH BOLLARD, WHILE DETAIL 10 INDICATES A 3'-6" HEIGHT. CLARIFY.
3. SHEET A-12; TANK PLAN 2: PROVIDE A NORTH ARROW ON THE PLAN.
4. SHEET A-12; TANK PAD SECTION 12: PROVIDE A DIMENSION ON THE SECTION INDICATING THE CLEAR DISTANCE FROM THE TOP OF THE SLAB TO THE UPPER REBAR.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.