Review Details: WALLS - ZONING/ENGINE

Permit Number - T14BU01115
Review Name: WALLS - ZONING/ENGINE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/16/2015 SPOWELL1 ENGINEERING REVIEW Needs Review
01/16/2015 SPOWELL1 BUILDING-RESIDENTIAL REVIEW Needs Review
11/21/2014 MICHAEL ST. PAUL ZONING REVIEW Reqs Change P&DS TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T14BU01115
4463 East Cooper Circle
7'-0" wall


TRANSMITTAL: November 21, 2014


COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).


This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 - 9.

The maximum height of a wall or fence within a perimeter yard shall be six (6) feet (UDC Section 6.6.2.I). The maximum height of a retaining wall is ten (10) feet from design grade and no higher than six (6) feet measured from the top of the retaining portion of the wall (UDC Section 6.6.2.I.2). The proposed wall height is seven (7) feet.