Permit Number: T14BU01057
Parcel: 10512020C

Address:
4144 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T14BU01057
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
10/17/2014 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Sheet 1 of 1

No comments.

Sheet 2 of 2

1. In Scope of Work, Existing Side View, and New Side View use previously
accepted term "backrail" instead of "walkrail".

2. Add paragraph in Scope of Work to address necessary shortening of
vertical runs of conduit and associated wiring and removal and installation
of any conduit and wiring with indication of points of disconnect.

3. In sixth paragraph of Scope of Work, New South Sign Face Elevation, New
Side View, indicate reduction in the number of spacers, stringers,
horizontal battens, and Z-Clip pairs to be proportionate to the reduced
vertical measure of the wood sections.

4. In New Side View, the vertical dimension as to the relocated backrail is
greatly out of scale with the rest of the detail; correct dimension or
backrail location as applicable.

5. Add standard electrical note: any excess fixtures, conduit, connections,
wiring, or breakers, no longer being used to be removed.

6. Add standard electrical note: no junction boxes or other fixtures where
wire connections are made shall be added or replaced other than those shown
on the plan.

Sheet 3 of 3

1. Add standard Z-clip detail.

2. In New Face Panel Section Detail and New Access Ladder Detail, reduce
the number of spacers, angle iron stringers, horizontal battens, and Z-Clip
pairs, as applicable, to be proportionate to the reduced vertical measure of
the wood sections.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/27/2014 CPIERCE1 REJECT SHELF Completed