Permit Number: T14BU00861
Parcel: 130140370

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T14BU00861
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Completed
09/30/2014 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Completed BRC Comments

Below are comments on the electrical repair resubmittal for COT ID# 302 at
1431 South Alvernon Way (T14BU00861).

Sheet 1 of 1

1. It appears that the utility pole located on APN 130-14-0360 and that had
provided service to the subject billboard was removed as a result of a
decision of the property owner to put the property to a different use (a
drainage basin) that was related to new development on APN 130-14-039C.
Furthermore, the record shows no easement running in favor of the utility
company having been conveyed in the location of the utility service pole.
However, given that electrical service had been provided to the subject
billboard via an overhead line from a utility pole in the Alvernon
right-of-way as of 2007 and that relocation of this overhead service line to
a utility pole on private land was the result of a general replacement of
utility poles along the Alvernon right-of-way in 2011, termination of
utility service under these facts will be attributed to utility company
action. As such, the application for a change in configuration from
overhead to underground utility service will not be denied, provided the
following condition is added to the permit: "Issuance of this permit as to
reconnection and reconfiguration of electrical service due to removal of a
utility service pole located on private land is based on the particular
facts of this case and shall have no bearing on future applications".

Sheet 2 of 2

No comments.

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/30/2014 SHANAE POWELL OUT TO CUSTOMER Completed