Permit Number: T14BU00550
Parcel: 99999999B

Address:
2200 N FREEWAY

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T14BU00550
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/11/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
10/09/2014 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the required modification and authorized repair
resubmittal for COT ID# 535 at 2200 South Freeway (T14BU00550).

Sheet 1 of 3

No comments.

Sheet 2 of 3

1. In Scope of Work, delete twelfth paragraph on walkaround alteration that
was added in this revision; alternatively, provide response regarding
applicant's justification for this work under the Stipulation.

2. Add text in fifteenth paragraph added in Scope of Work specifying
replacement stiffener plates to be 1/4" (consistent with the plan
referenced).

Sheet 3 of 3

1. Delete three added walkaround details, if applicable to conform with
response to Comment #1 under Sheet 2.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/17/2014 AROMERO4 OUT TO CUSTOMER Completed