Permit Number: T14BU00550
Parcel: 99999999B

Address:
2200 N FREEWAY

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T14BU00550
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/28/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
06/23/2014 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the required modification and authorized repair
submittal for COT ID# 535 at 2200 South Freeway (T14BU00550).

Sheet 1 of 3

1. Insert a generalized form of the standard Billboard Note #9, such as
"The proposed repairs and alterations are required and/or authorized by the
Stipulation as specified on Sheet __."

2. Insert the standard Billboard Note #10: "The billboard shall not be
relocated".

Sheet 2 of 3

1. In Existing Side View and New Side View show full length of uprights and
provide respective vertical dimensions.

2. In Existing Side View and New Side View, show catwalk ledgers and
catwalks and provide clearance dimensions from the bottom of the wood
sections to the top of the catwalk ledgers and inner edge of the catwalks.

3. Add note that reinstallation of the top-mounted light fixtures, supports
and associated hardware and electrical parts is to be as per original plans
under Activity No. T10EL02152.

4. In Scope of Work, fifth paragraph, clarify if 1/2" A325 bolts are to be
removed and reinstalled are replaced with new like.

5. Add standard boxed note: "The billboard shall not be relocated".

6. Add standard boxed note: "No parts or components are to be removed,
installed, replaced, or reinstalled except as indicated".

7. In South Face Elevation title, indicate North Face same (or otherwise
explain any difference between the two faces).

Sheet 3 of 3

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/09/2014 CPIERCE1 REJECT SHELF Completed