Permit Review Detail
Review Status: Completed
Review Details: MECHANICAL
Permit Number - T14BU00523
Review Name: MECHANICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/22/2014 | MARTIN BROWN | FIRE | REVIEW | Denied | According to dimensions provided on the plan, the required 6" overlap of hood to appliances cannot be met. Refer to the 2012 International Mechanical Code for possible solutions. |
| 06/17/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Verify the size of the hood canopy with respect to the appliance dimensions. Reference: Sections 507.1 (exception 1) and 507.12, IMC 2012. |