Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T14BU00194
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/08/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1) Notes on pp SP1 call for panic hardware 54" minimum above finished floor. This is a violation of IBC section 1008.1.9.2 2) Detail for picket gate and fence on SP2 calls for minimum 48" height which is in direct conflict with notes calling for a minimum 5' height. 3) Indicate and detail all accessible routes in and out of pool area. 4) Clarify how you get the a wheel chair to an area of refuge down what is shown as steps 5) Show all required accessible access points and clarify all accessible access equipment that may be used. 6) Due to repeated failures to provide complete and accurate plans and Per Secton 107.1 of the International Building Code All documents presented for submittal shall be prepared and sealed by a registered design professional. |