Permit Number: T14BU00194
Parcel: 11504520B

Review Status: Completed

Review Details: POOL - COMM MODEL

Permit Number - T14BU00194
Review Name: POOL - COMM MODEL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/14/2014 DAVID RIVERA ZONING REVIEW Approved
02/14/2014 LOREN MAKUS ENGINEERING REVIEW Approved
03/18/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Reqs Change It is the applicants responsibility to provide the correct submittal documents for review and approval. The generic sturctural design computations provided from AmmTec are full of information for pools installed in-ground, which does not apply to this project. Clarify on your plan set how these strucural calculations will be applied to this structure. (IBC 107)

2. PP SP-5 is largely illegible. Provide clean plan sheets with legible copy. (IBC 107.2)

3. Specify the type of lighting to be installed. Include cut-sheets and sufficient information to show compliance with the City of Tucson Outdoor lighting Code.

4. Panic hardware will be required for egress from this assembly pool area. Specify that on the plan sets. (IBC 1008.1.10)
03/18/2014 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Completed
03/18/2014 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Completed
03/18/2014 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Completed