Permit Review Detail
Review Status: Completed
Review Details: POOL - COMM MODEL
Permit Number - T14BU00194
Review Name: POOL - COMM MODEL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2014 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 02/14/2014 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 03/18/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | It is the applicants responsibility to provide the correct submittal documents for review and approval. The generic sturctural design computations provided from AmmTec are full of information for pools installed in-ground, which does not apply to this project. Clarify on your plan set how these strucural calculations will be applied to this structure. (IBC 107) 2. PP SP-5 is largely illegible. Provide clean plan sheets with legible copy. (IBC 107.2) 3. Specify the type of lighting to be installed. Include cut-sheets and sufficient information to show compliance with the City of Tucson Outdoor lighting Code. 4. Panic hardware will be required for egress from this assembly pool area. Specify that on the plan sets. (IBC 1008.1.10) |
| 03/18/2014 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 03/18/2014 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/18/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Completed |