Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T14BU00180
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T14BU00180
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2014 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
04/04/2014 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the electrical repair resubmittal for COT ID# 133 at
7218 East Broadway Boulevard (Stipulation Address) (T14BU00180).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Comment #2 on the original submittal was not fully responded to; provide
graphic detail that shows the location of the weatherhead on COT #133 and
sufficient clearance from the wood side panel that the conductors and ground
now appear to rest on. Note that the submittal and field inspection show the
triplex attachment to be hidden from view by the wood side panel and trim.

2. If the wood side panel referred to in Comment #1 above is to be
permanently removed, revise the added comment in the third paragraph of
Scope of Work; otherwise describe how side panel will be trimmed to provide
sufficient clearance for the conductors and ground.

3. The revised North Face Sign Elevation COT #116 incorrectly shows the
meter/panel backing assembly attached to the north face of the (west)
I-beam; correct the depiction to show the attachment to the east face of the
I-beam (as was shown in the original submittal).

Final Status

Task End Date Reviewer's Name Type of Review Description
06/10/2014 CPIERCE1 REJECT SHELF Completed