Permit Number - T14BU00180
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 02/24/2014 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments for the electrical repair submittal for COT ID# 133 at 7218 East Broadway Boulevard (Stipulation Address) (T14BU00180). Sheet 1 of 2 No comments. Sheet 2 of 2 1. Provide gauge, other standard wire descriptions, and whether a ground wire is included for the existing and replacement triplex wire. 2. Provide detail on how the triplex wire connects into the electrical parts attached to the COT #133 structure. 3. Clarify in Scope of Work whether any parts on the COT #133 structure are to be removed or reinstalled in order to replace the triplex. 4. Indicate minimum clearance for droop in triplex wire. 5. Load Calcs appear to include 25% load factor; add note to clarify. 6. In Electrical Riser Diagram, the riser conduit shown appears to be that which services COT #116; provide side view or otherwise better detail that distinguishes the two risers and the wiring contained therein. 7. In North Face Sign Elevation COT #116, the riser and weatherhead for #133 appear to be on the wrong side of the beam; correct in conjunction with addressing Comment #6 above. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/11/2014 | CPIERCE1 | REJECT SHELF | Completed |