Plan Number: T13SE00096
Parcel: Unknown

Review Status: Completed

Review Details: REZONING - IPC

Plan Number - T13SE00096
Review Name: REZONING - IPC
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2013 LAITH ALSHAMI ENGINEERING REVIEW Completed Laith Alshami, Engineering and Floodplain Review, 09/09/2013,

TO: Peter McLaughlin FROM: Laith Alshami, P.E.
Rezoning Section Engineering


SUBJECT: Family Attic - Pantano Road
Special Exception Case SE-13-96, T14S, R15E, SECTION 17
Reference: T13PRE0028

RECEIVED: Special Exception Preliminary Development Plan on September 3, 2013

The Preliminary Development Plan appears to have adequate Engineering and Floodplain related information to be forwarded to the rezoning examiner. No special conditions are offered.
09/10/2013 STEVE SHIELDS ZONING REVIEW Completed PDSD TRANSMITTAL

TO: Rezoning Division
Re: Acceptance of Information for Plan Compliance (IPC)

FROM: Steve Shields
Lead Planner

PROJECT: Family Attic - Retail/Household Goods Donation Center
1060 S. Pantano Road - C-1
Special Exception - SE-13-96

TRANSMITTAL: September 10, 2013

The proposed "Household Goods Donation Center", located on parcels 134-14-020E, zoned C-1. The use falls under UDC Table 4.8-4: Permitted Uses - Commercial and Mixed Use Zones - Permitted under Zoning Examiner Special Exception Procedure Section 3.4.3. The following Use Specific Standards apply: C-1: 4.9.5.G.2, .6 -12, 4.9.13.A.2, .B-D, and 4.9.13.O

1. The following dimensional Standards apply see UDC Table 6.3-4.A DIMENSIONAL STANDARDS FOR THE C-1, C-2, C-3, OCR-1, & OCR-2 ZONES

a. Minimum site area = 0 Sq. Ft.
b. Proposed site area = Not Provided (Existing)
c. Maximum building height allowed = 30 feet
d. Building height proposed = N/A (No new buildings proposed)

2. The submitted plan, showing the Household Goods Donation Center is acceptable to continue the review for the zoning examiner's report.

If you have any questions about this transmittal, please call Steve Shields, (520) 836-4956 or email Steve.Shields@tucsonaz.gov.
09/11/2013 JOHN BEALL COMMUNITY PLANNING REVIEW Completed DEPARTMENT OF PLANNING AND DEVELOPMENT SERVICES
SE-13-96 Family Attic- Pantano Road
C-1 Christian Family Care
Pantano East Area Plan
09/12/13 mt, ipc-review

This is a request for a special exception to allow the expansion of existing retail/household goods donation center on a property zoned C-1 (Neighborhood Commercial) that is developed as a multi-tenant commercial complex. Access is provided from Pantano Road on the east side of the special exception site, with on-site parking provided along the front and rear of the existing building. A six foot tall masonry wall is located on the north property line, adjacent to the special exception site.

According to the Major Streets and Routes Plan, Pantano Road is designated as an arterial street.

Surrounding Land Uses and Zones: The property to the south is zoned C-1 Neighborhood Commercial and currently a vacant gas station site, properties to the east across Pantano Road are zoned C-1 Neighborhood Commercial and developed with a medical office complex and a United States Post Office Center, the immediate property to the north is zoned C-1 Neighborhood Commercial developed with a single commercial building and north across Pantano Road is zoned R-2 and O-3 and developed as a multi-family complex.

Special Exception Presubmittal Meeting:
The applicant attended a special exception presubmittal conference meeting with city staff on May 22, 2013. At the meeting, staff discussed a variety of issues that would need to be addressed: security management plan; design compatibility statement; screening and buffering along residential edge, hours of operation and no outdoor storage, lighting, new dumpsters, vehicular circulation and parking, and location of noise generating uses. A plan amendment is not required for special exception to proceed
Neighborhood Meeting:
An on-site neighborhood meeting was held at 1066 S Pantano Road, on July 2, 2013 at 6:00 pm. The sign-in sheet shows that only the representatives, Kristi Wilbur and Penny Prette, from Family Attic were in attendance. No other attendees arrived, meeting adjourned at 6:20 p.m.

Land Use Plan Policy Summary:
The General Plan and the Pantano East Area Plan (PEAP) provide policy direction for this site.

The General Plan:
The General Plan Policy supports commercial uses at intersections of streets. The existing commercial complex meets Plan policy to be compatible in size, scale, and mass with adjacent uses. Commercial and Office Development policy supports appropriate locations for commercial and office uses, with priority for development and redevelopment within the existing urbanized areas to promote use and improvement of existing infrastructure, to increase pedestrian activity and transit use, and to meet residents' needs for goods and services in a cost-effective and equitable fashion. Conservation, Rehabilitation, and Redevelopment Policies call for economic viability of existing neighborhoods and commercial districts, to use and improve existing infrastructures, increase pedestrian activity and transit use, retain small businesses, and meet residents' needs for goods and services in a cost-effective and equitable fashion. Economic Development Policy is to encourage the expansion and continued viability of trade and service activities and to assist local firms in the trade and service sectors to expand their existing markets.

The Pantano East Area Plan:
PEAP Commercial Policy supports commercial developments in appropriate locations in the area and discourages the extension of strip commercial as a pattern of development and commercial uses and should be designed to be in harmony with adjacent residential uses.

Design Guidelines Manual encourages the 'Good Neighbor' approach -A solution is to encourage limited duration of activities that generate excessive noise, light or traffic by concentrating such activities between 10:00 a.m. and 6:00 p.m.; and limiting hours of operation where possible.

Discussion

Both the Pantano East Area Plan (PEAP) and the General Plan support commercial uses at this site due to its location on Pantano Road, designated as an arterial street on the Major Streets and Routes Plan. PEAP supports commercial developments in appropriate locations in the area, discourages the extension of strip commercial as a pattern of development and supports the integration of adjoining commercial uses to be designed in harmony with adjacent residential uses. The General Plan reinforces the direction provided by PEAP.

The applicant included a site plan that shows an existing commercial center with on-site parking and circulation. Primary access for the site is from Pantano Road, an arterial street to the east with a secondary access point from 22nd street to the south. The subject site has C-1 commercial zone with existing buildings. The site is an existing retail strip center with a proposal to expand the thrift store into two adjacent suites. An aerial taken in 2012 shows perimeter landscaping, and masonry wall along a portion of the northern perimeter, which buffers and screens the multi-family residential uses located to the north. Staff requests at the time of a full review for the Design Compatibility Report (DCR) to address any outdoor activity such as but not limited to; hours of operation, any new outdoor security lighting, and location of loading zone/drop-off areas if to be located outdoors at rear of building. Final staff support will be based on the proposed buffering and screening adjacent less intense land uses.

The proposal as submitted is in general compliance with the Pantano East Area Plan and the General Plan. A plan amendment is not required.

Recommendation
It is recommended that this request be accepted for processing. The Special Exception request is to allow the expansion of existing retail/household goods Donation Center into two adjacent suites of an existing site and utilizing existing infrastructure to meet residents' needs for goods and services in a cost-effective and equitable fashion.
Staff recommends the following issues be addressed at the time of Special Exception submittal as part of mitigating a non-retail donation center in the C-1 neighborhood commercial zone:
" Identify location for required landscape borders
" Identify location of screened/wall dumpster location
" Identify location of commercial vehicle loading zone
" If loading and unloading is to occur outdoors, please identify area and how employees/volunteers will be screened from direct sun light.
" Commercial vehicle route (circulation) to loading zone from Pantano Road.
" No overnight parking of commercial vehicles
" No outdoor storage.
" If loading/unloading is planned along the rear of the building, then provide Design Compatibility Report to address hours of operation and mitigation of noise generated from commercial activity onto adjacent multi-family complex located to the north
" If ancillary outdoor use is proposed such as sorting, boxing, loading, staff recommends the applicant address an outside working area for employees/volunteers, which provides protection from the direct sunlight.


Applicable Policy

Plan Policies
Pantano East Area Plan (PEAP) Commercial Policy 1 promotes commercial development in appropriate areas. Policy 2 is to discourage the extension of strip commercial as a pattern of development. Implementation Technique B. is to ensure that future commercial development be restricted to a limited number of access points, integrated with adjacent commercial development, and designed in harmony with adjacent residential uses.

The General Plan:
Element 2; Commercial and Office Development, Policy 5;
Support appropriate locations for commercial and office uses, with priority for development and redevelopment within the existing urbanized area located in the Central Core and Mid-City Growth Areas and the abutting areas of the Evolving Edge Growth Area to promote use and improvement of existing infrastructure, to increase pedestrian activity and transit use, and to meet residents' needs for goods and services in a cost-effective and equitable fashion. Supporting Policy 5.2 supports community-scaled commercial and office uses located at the intersections of arterial streets, taking into consideration traffic safety and congestion issues.

Element 6; Conservation, Rehabilitation, and Redevelopment
Policy 3.3 - Provide for a continue economic viability of existing neighborhood and commercial districts by promoting safety and maintenance programs and by encouraging appropriate new development.

Policy 4 - Support appropriate locations for commercial and office uses, with priority for development and redevelopment within the existing urbanized area, in order to use and improve existing infrastructure, increase pedestrian activity and transit use, retain small businesses, and meet residents' needs for goods and services in a cost-effective and equitable fashion
Supporting Policy 4.5 - Encourage the redevelopment of current strip commercial development that will improve traffic flow, pedestrian mobility and safety, and streetscape quality

Element 13: Economic Development, Policy 7; Encourage the expansion and continued viability of trade and service activities
Support Policy 7.2 Assist local firms in the trade and service sectors to expand their existing markets.

Design Guidelines Manual

Design Guideline I.A.5.c, 'Good Neighbor' Approach - The intent is to encourage businesses to be 'good neighbors' to adjacent residences. A solution is to encourage limited duration of activities that generate excessive noise, light or traffic by concentrating such activities between 10:00 a.m. and 6:00 p.m.; and limiting hours of operation where possible.
09/12/2013 KEN BROUILLETTE FIRE REVIEW Approved