Plan Number: T13PI00024
Parcel: Unknown

Address:
7600 S KOLB RD

Review Status: Completed

Review Details: PIA - RESUBMITTAL

Plan Number - T13PI00024
Review Name: PIA - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/18/2015 LINZUNZA UTILITY CLEARANCES COT STREETS DIVISION Completed
05/18/2015 LINZUNZA UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
05/18/2015 LINZUNZA UTILITY CLEARANCES PC WASTEWATER MGMT Completed
05/18/2015 LINZUNZA UTILITY CLEARANCES QUEST COMMUNICATION Completed
05/18/2015 LINZUNZA UTILITY CLEARANCES COX COMMUNICATION Completed
05/18/2015 LINZUNZA UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
05/18/2015 LINZUNZA UTILITY CLEARANCES EL PASO NATURAL GAS Completed
05/18/2015 LINZUNZA UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
06/15/2015 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approv-Cond
06/15/2015 LINZUNZA PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
06/15/2015 LINZUNZA PIA COORDINATOR OUT TO CUSTOMER Completed
07/16/2014 LINZUNZA UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
07/22/2014 GARY WITTWER DOT LANDSCAPE REVIEW Denied In my last review I noted that if you were to place private irrigation lines under public roadways you would be required to have an easement. This process has been discontinued and you can no longer do this. The irrigation systems will need to be re-designed.
Please coordinate with the signage plans. Trees must be set back 50 feet from a stop sign within the ROW for the approaching vehical. This is a major safety issue.
I am not sure that the City is required to notify you of all utility work - that would be up to the Director.
09/19/2014 JOSE ORTIZ DOT TRAFFIC REVIEW Denied September 19, 2014

PROJECT NAME: La Estrancia De Tucson - Camino Boleadoras & Via Bombachas (2nd Submittal)
PLAN #: I-2006-036
ACTIVITY NUMBER: T13PI00024
PROJECT REVIEWER: Simon Ramos, EIT, Traffic Engineering, City of Tucson DOT

The Signing and Striping Section has completed the reviewed of the PIA plan and does not recommend approval at this time. The following comments need to be addressed in the subsequent plan submittal. Please return redlined drawings with next submittal and reference PIA activity number on all correspondences.

1. On page 1 of 3, Striping Notes #6 and #7, DELETE "hot-sprayed".

2. On page 1 of 3, Striping Notes #8 - DELETE "following control points that have been set no more than 50 feet apart along the lines to be striped in tangent section of a road where the pavement marking pattern does not change, control points can be set at 200 feet apart."

3. On page 1 of 3, Striping Notes #11 - Fix indent.

4. On page 1 of 3, Striping Notes #15 - DELETE all, it is a repeat.

5. On page 2 of 3, ADD "Shop drawings for all signs including street name signs shall be submitted
to Traffic Engineering (Diahn Swartz 520-791-4259) for approval before fabrication." in General Notes.

6. On page 2 and 3 of 3, DELETE all "No Parking Signs".

7. On page 2 of 3, REPLACE "W6-2" Sign with "W6-1" Sign as noted on red-lines.

8. On page 2 of 3, REPLACE "PER STD. DTL 5-14" with "Pavement Marking Design Manual Sheet 5-14"

9. On page 2 and 3 of 3, Indicate YS4 installed 1 foot offset from curb.

10. On page 2 of 3, Speed Limit 30 MPH per Signing Notes and dimensions are 24x30..

11. On page 2 and 3 of 3, Indicate all signing dimensions.

12. On page 2 and 3 of 3, REMOVE all "Stop Signs" where indicated on red-lines.

13. On page 2 of 3, Mount "Bike Route" sign on same post of "Speed Limit" sign as indicated on red- lines.

14. On page 2 of 3, ADD signing where indicated on red-lines.

15. On page 3 of 3, REMOVE all pavement markings on Via Bombachas and Via Pampas Morenas.

16. On page 3 of 3, Improve visibility of street name signs by locating closer to intersection per red- lines.

17. On page 3 of 3, REMOVE "R3-8LR" signs as indicated on red-lines.

18. On page 3 of 3, Need Guidance that road does not continue to Julian Wash. Suggestion on red- lines. (4 x OM4-3).
19. Fix station 28+07.57?

Please Refer to redline plans for additional comments and comment details. If you have any questions, I can be reached at 837-6678 or Simon.Ramos@tucsonaz.gov
10/17/2014 RICHARD LEIGH DOT ENGINEERING REVIEW Approved