Plan Number: T13PI00022
Parcel: Unknown

Address:
7600 S KOLB RD

Review Status: Active

Review Details: PIA - SUBMITTAL

Plan Number - T13PI00022
Review Name: PIA - SUBMITTAL
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2014 RICHARD LEIGH DOT ENGINEERING REVIEW Denied SUBJECT: La Estancia De Tucson - Lots 1-330 I-2006-015

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend a conditional approval. The following comments need to be addressed prior to in the subsequent review submittal. Please return redlined drawings with next submittal.


1. Include Development Services Department PIA activity number "T13PI00022"on cover sheet.

2. Align curb access ramp so that they are directly across from each other per section 10-01.3.3.E of the U.D.C. Technical Manual.
3. Indicate the ending and beginning of all proposed barricade railing.
4. Indicate the class of pipe for all proposed storm drains.
Please Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
01/03/2014 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied We have reviewed this plan and have the following comments:

1. Several pages show drainage channels with scuppers. Some channels appear to be rip rap while others appear to be concrete. Some of these are listed as common area and other aren't. Who is responcible for the maintenace of these drainages? If these are rip rap what is D50 and the thickness of the rip rap layer.

No further comments.

Lance Peterson, P.E.
Streets and Traffic Maintenance
837-6777
12/02/2013 BESPINO1 UTILITY CLEARANCES COT STREETS DIVISION Denied
12/02/2013 ANY PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Active
12/02/2013 BESPINO1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
12/02/2013 ANY PIA COORDINATOR OUT TO CUSTOMER Active
12/02/2013 BESPINO1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied
12/02/2013 BESPINO1 UTILITY CLEARANCES QUEST COMMUNICATION Denied
12/02/2013 BESPINO1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
12/02/2013 BESPINO1 UTILITY CLEARANCES COX COMMUNICATION Denied
12/02/2013 BESPINO1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
12/02/2013 BESPINO1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied
12/02/2013 BESPINO1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied
12/10/2013 JOSE ORTIZ DOT TRAFFIC REVIEW Denied PLANS # i-2006-015
ACTIVITY NUMBER: T13PI00022
PROJECT NAME: La Estancia De Tucson lots 1-330
PROJECT ADDRESS: 7600 S Kolb Rd
PROJECT REVIEWER: Matthew Geweke, Traffic Eng. Tech

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal. The following items must be revised or added to the plan. Please include a response letter with the next submittal that states how all comments have been addressed and resubmit the original redline set of plans for back checking purposes.

1. Need Signing & Striping Shts for all the public streets.

2. Sht 2: Please update the Signing & Striping Notes - see attchments.

3. Sht 3: Please make the Bike Routes lanes 6' wide as per current TDOT Standards. Change value throughout the rest of the plans accordingly.

4. Please remove all gray scale shading from signing/striping plans.

5. Sht 26: Please make redline changes to plans as indicated.

6. Please add 'St. Name Sign Info' to plans. See attached example.

7. Between Phase I & Phase II you will need to install standard bollards if more than a 1 year delay, or less than a 1 year delay 'end of road" markers on posts would be fine. See sht 26 for a redline note.

If you wish to email me at Matthew.Geweke@tucsonaz.gov with a PDF of redlines and the corrected Shts with the revisions of these requested changes, we could expedite the Traffic Eng. acceptance/approval of these plans.

I can also be reached in the office at 837-6665 with any questions.
Thanks
12/11/2013 GARY WITTWER DOT LANDSCAPE REVIEW Denied Please submit the irrigation plans for common areas. Remember that if you place private irrigation lines under public roadway, you must create an irrigation easement at that location. Let me know if you have questions.