Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: T13PI00010
Parcel: Unknown

Address:
3300 S PARK AV

Review Status: Completed

Review Details: PIA - SUBMITTAL

Plan Number - T13PI00010
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/03/2013 JOSE ORTIZ DOT TRAFFIC REVIEW Denied i-2013-010
ACTIVITY NUMBER: T13PI00010
PROJECT NAME: The Bridges Blk 10
PROJECT ADDRESS:
PROJECT REVIEWER: Matthew Geweke, Traffic Eng Tech

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal. The following items must be revised or added to the plan. Please include a response letter with the next submittal that states how all comments have been addressed.

1. See redlines on the submitted drawing Shts 9 & 10 and address the additional redline comments.
(A) Sht 9: modify the Tucson Marketplace Blvd striping to standard.
(B) Sht 10: remove unnecessary 25mph & Stop signs.
(C) Sht 10: add proper Tucson Marketplace Blvd turn bay signs.
During the next submittal please re-submit the original roll of redlines for back checking purposes.

2. Please include omitted signing and striping notes on plans as needed. See redline notes and attachments.

If you wish to email me (Matthew.Geweke@tucsonaz.gov) a PDF of Shts 9 & 10 with the revisions of these requested changes, we could expedite the Traffic Eng. acceptance of these plans.

I can also be reached at 791-4259 x76665 with any questions.
Thanks!
Matthew Geweke
07/03/2013 BESPINO1 UTILITY CLEARANCES COT STREETS DIVISION Denied
07/03/2013 BESPINO1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
07/03/2013 BESPINO1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied
07/03/2013 BESPINO1 UTILITY CLEARANCES QUEST COMMUNICATION Denied
07/03/2013 BESPINO1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
07/03/2013 BESPINO1 UTILITY CLEARANCES COX COMMUNICATION Denied
07/03/2013 BESPINO1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
07/03/2013 BESPINO1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied
07/03/2013 BESPINO1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied
07/15/2013 GARY WITTWER DOT LANDSCAPE REVIEW Denied Thanks for including the NPPO Plans.
1. It appears that there are common areas on the plan. Will they be landscaped and will they have irrigation? Please remember that private irrigation lines can not cross public roadway. (unless you get an irrigation easement)
2. Please submit Landscape and irrigation plans for Common Areas.
07/24/2013 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied I have reviewed this plan and have the following questions:

1. The note call out the use of mix number 1 and mix number 2 for the project. I did not see where the differnet mixes will be used.

2. There are different common areas called out on the plans. Common Area "C" is listed as a private drainage but Common Area "A" and "B" are not labeled. Who is responcible for the maintennance of these common areas?

No further comments.

Lance Peterson, P.E.
Streets and Traffic Maintenance
837-6777
08/08/2013 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
08/08/2013 RICHARD LEIGH DOT ENGINEERING REVIEW Approv-Cond Please address red line comments prior to submittal of mylar plan set for final approval.

Call me if you have ay questions

Richard Leigh
837-6647
08/08/2013 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed