Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: T13PI00001
Parcel: Unknown

Review Status: Completed

Review Details: PIA - RESUBMITTAL

Plan Number - T13PI00001
Review Name: PIA - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/29/2013 JOSE ORTIZ DOT TRAFFIC REVIEW Approv-Cond just a few minor tweaks to the redlines and we are good!

on Sht. 2 Keynote #14 please add "Name" where indicated to text.

on Sht. 5;
- if possible please move the STOP sign over just a bit, make it less of a pedestrian obstacle.
- please designate Tyndall as a N street
- keynote #9 please just fill the blanks


any questions, please feel free to email or call
thanks,
Matthew.Geweke@tucsonaz.gov
791-4259
09/06/2013 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
09/11/2013 BLANCA ESPINO PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
09/11/2013 GARY WITTWER DOT LANDSCAPE REVIEW Approved
09/11/2013 BLANCA ESPINO PIA COORDINATOR OUT TO CUSTOMER Completed
09/11/2013 RICHARD LEIGH DOT ENGINEERING REVIEW Approv-Cond September 10, 2013

SUBJECT: The HUB at Tucson - Public Improvements

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and recommends a conditional approval at this time. The following comments need to be addressed prior to submittal of mylar plan set for final review and approval.

1. Sheet 4: The vertical to wedge curb transitions at the sidewalk scupper at station 10+87.96, LT (Tyndall Ave) are inaccurately depicted. Per Std. Dtl. 210 the gutter line should remain consistent through the transition. Revise accordingly.

2. Sheet 6, Hardscape Sections: Reference City of Tucson Standard Detail 201 for the brick pavers. Also, specify the proposed brick pattern.

3. Sheet 6, Detail 7: Show how steel plate over the bubbler box will be supported, Sta. Dtl. 205 limit span to 2.5'.

4. Indicate on plan, as a general note and on the detail, that the abutting property owner will be responsible maintenance for the bubbler box.

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
11/13/2013 BESPINO1 UTILITY CLEARANCES COT STREETS DIVISION Completed
11/13/2013 BESPINO1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
11/13/2013 BESPINO1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
11/13/2013 BESPINO1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
11/13/2013 BESPINO1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
11/13/2013 BESPINO1 UTILITY CLEARANCES COX COMMUNICATION Completed
11/13/2013 BESPINO1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
11/13/2013 BESPINO1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
11/13/2013 BESPINO1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed