Review Details: PIA - SUBMITTAL

Plan Number - T13PI00001
Review Name: PIA - SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/30/2013 JOSE ORTIZ DOT TRAFFIC REVIEW Denied ACTIVITY NUMBER: T13PI00001
PLANS # U-2013-001
PROJECT NAME: The Hub at Tucson
PROJECT ADDRESS: Tyndall Ave & First St
PROJECT REVIEWER: Matthew Geweke

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal.

The following items must be revised or added to the plan.

- Include a response letter with the next submittal that states how all comments have been addressed.

- See redlines on the submitted drawings and address the additional redline comments. During the next submittal and please re-submit the roll of redlines for back checking purposes.

- Must offer redline review to ParkWise (791-5071) for review of Parking Permit Prog. Signs

If you have any questions, I can be reached at 791-4259 or Matthew.Geweke@tucsonaz.gov or my supervisor Jose.Ortiz@tucsonaz.gov
01/30/2013 GARY WITTWER DOT LANDSCAPE REVIEW Approved
02/13/2013 RICHARD LEIGH DOT ENGINEERING REVIEW Approv-Cond February 13, 2013


SUBJECT: The HUB at Tucson - Public Improvements

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and recommends a conditional approval at this time. The following comments need to be addressed prior to submittal of mylar plan set for final review and approval.

1. Include the plan number "U-2013-001" in the title block of each sheet.

2. Include Development Services Department PIA activity number "T13PI00001"on cover sheet.

3. A Temporary Revocable Easement will be required for the for the proposed steps on 1st St.

4. Sheet 5 Detail 2; The maximum allowable slope for the wings on ramp is 1:12

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
02/27/2013 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approv-Cond We have reviewed this plan and have approved it conditionally. The only concern is with the brick pavers in the sidewalk area. Are these going to be standard brick pavers or specialty pavers for this project? Thanks

Lance Peterson, P.E.
Streets and Traffic Maintenance
520-837-6777
03/01/2013 BLANCA ESPINO PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
03/01/2013 BESPINO1 UTILITY CLEARANCES COT STREETS DIVISION Denied
03/01/2013 BLANCA ESPINO PIA COORDINATOR OUT TO CUSTOMER Completed
03/01/2013 BESPINO1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Denied
03/01/2013 BESPINO1 UTILITY CLEARANCES PC WASTEWATER MGMT Denied
03/01/2013 BESPINO1 UTILITY CLEARANCES QUEST COMMUNICATION Denied
03/01/2013 BESPINO1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Denied
03/01/2013 BESPINO1 UTILITY CLEARANCES COX COMMUNICATION Denied
03/01/2013 BESPINO1 UTILITY CLEARANCES SOUTHWEST GAS CORP Denied
03/01/2013 BESPINO1 UTILITY CLEARANCES EL PASO NATURAL GAS Denied
03/01/2013 BESPINO1 UTILITY CLEARANCES KINDER MORGAN ENERGY Denied