02/20/2014 ELIZABETH LEIBOLD ENGINEERING REVIEW Reqs Change DATE: February 20, 2014
TO: Rene Martinez-Flores, P.E.
SUBJECT: 10601 E CALLE NOPALITO Grading Plan Resubmittal Review
LOCATION: Rancho Del Este lot 283
REVIEWER: Elizabeth Leibold P.E.
ACTIVITY NUMBER: T13OT01453 AND T13CM05759

Summary: Engineering Division has reviewed the re-submitted plans and drainage statement under permits T13OT01453 AND T13CM05759. Engineering does not recommend approval of either permit until the following comments are addressed.

COMMENTS:
1) Tech Man Sec.4-04.2.2.5.A: Revise drainage statement to clarify FFE based on WSEL adjacent to proposed structure, including datum conversion for NGVD29 datum shift.
2) Tech Man Sec.4-04.2.3.1.5.B: Address the following drainage statement comments:
i) Fence appears to cross the wash and therefore shall show that 100-yr flows are conveyable beneath fence. Provide cross sectional analysis with flowrate computation for 100-yr conveyance under fence opening or revise location of fence on plans.
ii) Clarify proposed fence clearances on plans. Indicate the location of the proposed elevations of openings on the details and or planviews.
iii) Provide discussion and engineering justification in drainage statement regarding whether Erosion Hazard Setback is recommended or impacting proposed development. Analysis should be based on computed flowrate for 100-yr event. Also label EHS on plan view.
iv) There is also a reference to 42 inches for scour depth but no calculation was provided. Provide scour calculations referenced in statement.

I can be reached at 837-4934 if you have questions.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
City of Tucson