Permit Number: T13OT01453
Parcel: 133383000

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T13OT01453
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/10/2014 ELIZABETH LEIBOLD ENGINEERING REVIEW Denied DATE: January 10, 2014
TO: Rene Martinez-Flores, P.E.
SUBJECT: 10601 E CALLE NOPALITO Grading Plan Review
LOCATION: Rancho Del Este lot 283
REVIEWER: Elizabeth Leibold P.E.
ACTIVITY NUMBER: T13OT01453 AND T13CM05759

Summary: Engineering Division has reviewed the submitted plans under permits T13OT01453 AND T13CM05759. Engineering does not recommend approval of either permit until the following comments are addressed.

COMMENTS:
1) Admin Manual Sec.2-06.4.8: Show and label all data within lot boundary per Final Plat on planviews. Some data does not match plat; see sheet 2 of Final Plat and provide all delineations as shown within lot 283 boundaries. Data must be clearly drawn with dimensions / bearings if shown on Final Plat. See printout from final plat in package or see link for Final Plat at: http://tdotmaps.transview.org/MandR/MP/MPList.cfm?Plan=MP-29-052&Done=True
2) Tech Manual Sec.2-01.4.1.C.3: Delineate disturbance area on plan to assure disturbance/grading limits include all disturbance areas such as grading disturbance area, staging area, and construction area. Any disturbance areas that are found during inspections to exceed approved grading limits can cause delays for revisions to plans or stop-work-order.
3) Tech Man Sec.4-04.2.2.5.A: Provide drainage statement to clarify FFE based on WSEL adjacent to proposed structure.
4) Tech Manual Sec.2-01.4: Show flow arrows for general grading around proposed structure indicating positive gradients. Provide note on plan for proposed cut/fill quantities in cubic yards.
5) Tech Man Sec.4-04.2.3.1.5.B: Address the following drainage statement comments:
i) Clarify proposed wall openings in drainage statement and on plans. It appears that there is a wall or fence proposed that will have a series of openings at the bottom. Indicate the location of the proposed elevations on the details and or planviews.
ii) Provide discussion and engineering justification in drainage statement regarding whether Erosion Hazard Setback is recommended or impacting proposed development.
iii) A foundation depth of 42" below grade was stated in the Drainage Statement; clarify what this is referring to for the proposed design. There is also a reference to 42 inches for scour depth but no calculation was provided. Provide all calculations referenced in statement.
iv) Provide analysis for determining WSEL's.
v) There is reference to county and FEMA info for determining hydrologic data; provided reference and copies of documents in resubmittal.

I can be reached at 837-4934 if you have questions.

Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
City of Tucson

Final Status

Task End Date Reviewer's Name Type of Review Description
01/14/2014 FERNE RODRIGUEZ OUT TO CUSTOMER Completed
01/14/2014 CPIERCE1 REJECT SHELF Completed