Permit Number: T13OT01407
Parcel: 14043013A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T13OT01407
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/11/2014 ELIZABETH LEIBOLD ENGINEERING REVIEW Reqs Change TO: Michael Henrich, P.E., Chuck Pedri, P.E. PMP
SUBJECT: TIA Airport Traffic Control Tower Floodplain Resubmittal Review
REVIEWER: Elizabeth Leibold, P.E., CPM, CFM
DATE: February 11, 2014
ACTIVITY NUMBER: T13OT01407
SUMMARY: Engineering has received and reviewed the revised Drainage Report for the Tucson International Airport Traffic Control Tower, and recommends conditional approval.
ENGINEERING CONDITIONS OF APPROVAL:
1) Tucson Code Sec. 26-11.2(b)(4): The following shall be shown on grading plan or on sheets with resubmittal for T13CM07173.
a) Show tie in to channel embankment to EHS as discussed at counter meeting 21JAN14.
b) (g) Add general note to grading plan as stated in this response letter, or a permit condition will be added to permit, that offsite disposal location for overexcavated soils and other deleterious materials shall be placed in an approved and permitted site, and not located near or within the flood plain boundaries.
c) (h) Clarify construction access and permanent access locations on SWPPP plans as indicated in response letter to be reviewed with SWPPP with T13CM07273.
For any questions, call me at 837-4934.
Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning and Development Services Dept.
02/11/2014 ELIZABETH LEIBOLD ENGINEERING REVIEW Reqs Change Status updated to requires change -see comments.