11/04/2013 ELEIBOL1 ENGINEERING REVIEW Approved DATE: November 4, 2013
TO: Dave Koss
SUBJECT: Drainage Report Engineering Review
ADDRESS: Norma Lane and Dorothy Lane properties Adjacent to Stone Ave Wash
LOCATION: T13S, R13E, Section 24
REVIEWER: Elizabeth Leibold, P.E.
FLOODPLAIN INFO: FIRM Panel: 040191686L (eff: 16JUN11), SFHA zone: X, COT Floodplain
ACTIVITY NUMBER: T13OT01254


SUMMARY: PDSD Engineering Division has reviewed the revised RMJR drainage report sealed 11-1-13 for the Stone Avenue Wash and recommends approval. This project involves assessment of the floodplain and erosion hazard conditions affecting two COT real estate parcels adjacent to the Stone Avenue Wash channel. This floodplain use permit is for review only (not for construction). Separate elevation certificates will be generated under separate floodplain use permits for the parcel development. Diskette of final revised report shall be provided and one hard copy of the final report may be submitted to the City of Tucson for archive at PDSD Engineering. No additional fees should be assessed for documents that are required under a standard drainage report submittal. If you have any questions, call me at 837-4934.


Elizabeth Leibold, P.E., CPM, CFM
Civil Engineer
Engineering Division
Planning & Development Services Department
11/04/2013 ELEIBOL1 ENGINEERING REVIEW Approved Auxiliary surveyable limits for EHS and floodplain was prepared by the civil engineer and his surveyor for supplemental data for the report 26FEB14.