Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07814
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/30/2013 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/30/2013 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
| 12/30/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/30/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/30/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/30/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 12/30/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/30/2013 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 12/30/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/30/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/03/2014 | SHANAE POWELL | APPROVAL SHELF | Completed |
| 06/03/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |