Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM07775
Parcel: 12009157D

Address:
4510 S 3RD AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM07775
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/16/2014 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T13CM07775
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Projections may not extend to a point closer than 2 feet from the property line. Provide notation for compliance with R302.1 (City of Tucson Amended) by removing the roof overhang at the west wall that is visible on the north and south elevations.
2. Show a ½" gypsum board (garage side) on all walls common to the garage and house or other fire rated product in compliance with R309.2.
3. Enclose the two window openings with ½" gypsum board on framing or masonry similar to existing on all walls common to the garage and house, R309.2.
4. Show the garage floor direction of slope, R309.3.

STRUCTURAL PLANS:

1. Show a beam size with appropriate load carrying capacity, R301.1. The 4" x 6" beam at keynote #6 sheet 4 is under sized for the roof loading.

SECTIONS - DETAILS:

1. Clarify the location of the framed wall construction shown at detail #1 sheet 2, R106.1.1. Use the appropriate reference call-out on the Foundation Plan.
2. Clarify detail #4 sheet 6 showing ledger connection to a top plate or blocking.

MECHANICAL PLANS:

1. Provide protection of (indoor rated) equipment located outdoors with an exterior rated enclosure, G2406.3.
2. Provide heating facilities in all habitable rooms, R303.9. Show the location of keynote #5 sheet 8.
3. Show the existing bathroom exhaust fan location, R303.3 and M1507.3.

ELECTRICAL PLANS:

1. Show the location of the panel on the Electrical Plan, E3601.6.2 & E3705.8.
2. Show or notate a disconnect means or a locking breaker for the water heater, E4101.5.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Tucson is in climate zone 2B. The simplified prescribed energy values for glazing is U=0.40, skylights U=0.65, ceiling R=38 and walls R=13. Update or remove the skylight value on sheet 8, N1102.1.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
04/23/2014 CPIERCE1 OUT TO CUSTOMER Completed
04/23/2014 CPIERCE1 REJECT SHELF Completed