Permit Number: T13CM07772
Parcel: 110120910

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM07772
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/26/2013 CPIERCE1 ELECTRICAL-COMMERCIAL REVIEW Needs Review
12/26/2013 ROBERT SHERRY WATER REVIEW Approved
12/26/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. the exhaust fan shall operate whenever the supply air is operating). Reference: Section 403.2.1 (4), IMC 2012.
12/26/2013 CPIERCE1 FIRE REVIEW Needs Review
12/26/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/26/2013 CPIERCE1 WWM REVIEW Completed