Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07772
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/26/2013 | CPIERCE1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 12/26/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/26/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fan so that all of the air supplied to the restroom will be exhausted (i.e. the exhaust fan shall operate whenever the supply air is operating). Reference: Section 403.2.1 (4), IMC 2012. |
| 12/26/2013 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 12/26/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/26/2013 | CPIERCE1 | WWM | REVIEW | Completed |