Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07670
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Demonstrate energy code compliance for the alterations to the building envelope (e.g. the new exterior doors and the new roll-up door) based on the current code. Reference: Sections C101.4.3, C101.5, and C103.2, International Energy Conservation Code 2012. 2. Schedule the new split system air conditioner, FC-A/AC-A, and include it in the mechanical compliance certificate. |
| 01/02/2014 | ROBERT SHERRY | WATER | REVIEW | Denied | Verify that the addition of the equipment demand (3 evaporative coolers) and any hose bibbs will not cause the total demand to exceed 22.5 GPM, the maximum flow allowed by Tucson Water for a ¾" water meter. |
| 01/06/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T1.1; CODE ANALYSIS (GENERAL BUILDING SUMMARY): 943 SF IS DESIGNATED AS AN ASSEMBLY (A) OCCUPANCY CLASSIFICATION. SPECIFY WHICH GROUP WITHIN THE "A" CLASSIFICATION. 2. SHEET T1.1; CODE ANALYSIS (GOVERNING REGULATIONS): THE ACCESSIBILITY CODE SHOULD BE NOTED AS THE 2012 IBC AND THE 2009 ICC/ANSI A117.1. REVISE. 3. SHEET A1.1; FLOOR PLAN KEYNOTES: REVISE THE DETAIL REFERENCE IN NOTE 27. 4. SHEET A2.1; ELEVATION KEYNOTES: REVISE THE DETAIL REFERENCE IN NOTE 14 (6/AS1.1). 5. SHEET A5.1; ENLARGED RESTROOM (7): IT DOES NOT APPEAR THE SHOWER IS ACCESSIBLE, AS REQUIRED BY THE IBC SECTION 1109.2. VERIFY. PROVIDE DETAILS ON THIS SHEET FOR THE SEAT, GRAB BARS, AND CONTROLS PER THE ICC/ANSI SECTION 608. 6. SHEET S1.0 (DETAIL 101); SHEET S2.0 (LINTEL SCHEDULE): DETAIL 101 INDICATES THE VERTICAL LEG OF THE NEW BENT PLATE EXTENDS MORE THAN 24" VERTICALLY, WHILE THE LINTEL CL1 IN THE SCHEDULE INDICATES 16" VERTICAL LEGS. IS SECTION X ON S1.0 INDICATING THE STEEL PLATE LINTEL EXTENSION ON EACH END? CLARIFY ON THE DETAIL. 7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 01/06/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide tempered water for the lavatories and for public hand-washing sinks in restrooms using approved devices conforming to ASSE 1070 ( the temperature limit stop for the specified lavatory faucet does not conform to ASSE 1070). Reference: Sections 416.5 and 607.1.2, IPC 2012. |
| 01/09/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/30/2013 | KEN BROUILLETTE | FIRE | REVIEW | Denied | PLEASE PROVIDE INFORMATION ON OCCUPANCY CLASSIFICATION DETERMINATION. IT APPEARS THAT CUTTING/WELDING IS INVOLVED INSIDE THE SHOP AND WOODWORKING. PLEASE INDICATE COLLECTION PROCESS OF CUT MATERIAL PER IFC CHAPTER 22. PLEASE PROVIDE A HMIS FOR ANY CHEMICALS USED OR STORED |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/22/2014 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 01/22/2014 | CPIERCE1 | REJECT SHELF | Completed |