Permit Number: T13CM07569
Parcel: 13315058A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM07569
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2013 DAVID RIVERA ZONING REVIEW Approved
12/16/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the zone air distribution effectivness value (Ez) used in the ventilation calculations to 0.8 (ceiling supply, ceiling return) per Section 403.3.1.2, IMC 2012.
2. Revise the calculation of the system outdor intake flow rate (Vot) per Section 403.3.2.3, IMC 2012.
3. Show the balancing data for the supply diffusers (required for calculations involving multiple zone recirculating systems).
4. Show how the return air is to be accomodated. If the rooms are being used for massage therapy, a return will be required in each room.
12/16/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/16/2013 ROBERT SHERRY WATER REVIEW Approved
12/16/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Reqs Change THIS WORK IS TO EXPAND THE EXISTING "GARDEN OF EDEN" PLEASE PROVIDE SPECIFIC USES FOR THE ADDITIONAL ROOMS. FOR ESTABLISHMENTS WITH 4 OR MORE MASSAGE ROOMS THEN AT LEAST 2 RESTROOMS ARE REQUIRED PER CITY OF TUCSON MASSAGE LICENSING REQUIREMENTS.
12/16/2013 LOREN MAKUS ENGINEERING REVIEW Approved
12/16/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/16/2013 LHANLY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/18/2013 KEN BROUILLETTE FIRE REVIEW Approved
12/19/2013 FRODRIG2 WWM REVIEW Completed