Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07569
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/16/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 12/16/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Revise the zone air distribution effectivness value (Ez) used in the ventilation calculations to 0.8 (ceiling supply, ceiling return) per Section 403.3.1.2, IMC 2012. 2. Revise the calculation of the system outdor intake flow rate (Vot) per Section 403.3.2.3, IMC 2012. 3. Show the balancing data for the supply diffusers (required for calculations involving multiple zone recirculating systems). 4. Show how the return air is to be accomodated. If the rooms are being used for massage therapy, a return will be required in each room. |
| 12/16/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/16/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/16/2013 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | THIS WORK IS TO EXPAND THE EXISTING "GARDEN OF EDEN" PLEASE PROVIDE SPECIFIC USES FOR THE ADDITIONAL ROOMS. FOR ESTABLISHMENTS WITH 4 OR MORE MASSAGE ROOMS THEN AT LEAST 2 RESTROOMS ARE REQUIRED PER CITY OF TUCSON MASSAGE LICENSING REQUIREMENTS. |
| 12/16/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/16/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/16/2013 | LHANLY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/18/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 12/19/2013 | FRODRIG2 | WWM | REVIEW | Completed |