Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07547
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/13/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/13/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/13/2013 | RSHERRY1 | WWM | REVIEW | Passed | No wastewater plumbing. |
| 12/13/2013 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 12/16/2013 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 12/16/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/16/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/16/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/07/2014 | CPIERCE1 | APPROVAL SHELF | Completed |