Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T13CM07522
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM07522
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/03/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
01/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The two rooftop units are not ducted to the same areas of the store. Clarify how the two unis are able to operate in sequence and show the sequence of operation for the units on the drawings.