Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07522
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/03/2014 | KEN VAN KARSEN | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 01/03/2014 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/06/2014 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | The two rooftop units are not ducted to the same areas of the store. Clarify how the two unis are able to operate in sequence and show the sequence of operation for the units on the drawings. |