Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2014 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
01/03/2014 KEN VAN KARSEN ELECTRICAL-COMMERCIAL REVIEW Completed
01/06/2014 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied The two rooftop units are not ducted to the same areas of the store. Clarify how the two unis are able to operate in sequence and show the sequence of operation for the units on the drawings.