Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM07522
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM07522
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2014 GERRY KOZIOL WWM REVIEW Passed
12/12/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
12/13/2013 ROBERT SHERRY WATER REVIEW Approved
12/13/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM07522

1. Provide 2012 IECC Budget Lighting Calculation, required per C of T---- TI Submittal Requirements. ComCheck ok.

Ray Majuta
PDSD, Tucson
Elect Plan Review
12/13/2013
Ray.Majuta@tucsonaz,gov
12/13/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Provide justification for the heating and cooling capacities for the two rooftop units. Based on your load calculations, the units are oversized. Reference; section C403.2.2, IECC 2012.
2. Show that the proposed HVAC systems meet the control requirements of Sections C403.2.4 and C403.3. Reference: Section C303.1, International Energy Conservation Code 2012.
3. Show that the specified packaged air conditioning units meet the minimum efficiency requirements. Reference: Section C403.2.3, IMC 2012.
4. Show how the propsed design for the HVAC system provides for relief of the excess air outdor air during economizer operation. Reference: Section C403.3.1.1.3, IECC 2012.
5. Provide calculations to show that the proposed air conditioning units provide adequate ventilation using the current code. Reference: Section 403.2, IMC 2012.
12/13/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change Provide structural calculations for the Cashwrap soffit suspension system.
12/13/2013 JASON GREEN ENGINEERING REVIEW Approved
12/13/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved Show how the replacement water heater for the restroom lavatory will limit the water temperature to a maximum of 110 degrees Fahrenheit.
12/13/2013 MARTIN BROWN FIRE REVIEW Approved
12/13/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2014 SHANAE POWELL APPROVAL SHELF Completed
01/03/2014 SHANAE POWELL OUT TO CUSTOMER Completed