Permit Number: T13CM07510
Parcel: 112060420

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM07510
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/08/2014 RAFAEL CANCINO BUILDING-RESIDENTIAL REVIEW Completed PLAN REVIEW COMMENTS

Date: January 3, 2014
Activity: T13CM07510
Address: 2121 E. Mitchell
Applicant: East Coast Contractors


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the code references on the plans.

GENERAL NOTES:

" Limit all code references to those recognized by the City of Tucson. Adopted 2012 codes are listed at the Planning & Development Services web site. Show the code references used for the design.

FLOOR PLAN:

1. Provide window and door sizes.

ELEVATION PLANS:

1. Show existing grade, F.F.E and height of ridge.

DETAIL PLAN:

1. Provide weep holes in brick veneer, R703.7.8
2. Provide flashing at bottom of veneer, R703.7.5
3. Provide additional metal ties around openings that exceed 16 inches in either direction, R703.7.4.1.1

PLUMBING PLAN:

1. Install water hammer arrestors at washer and dish washer connections.

MECHANICAL PLAN:

1. Provide Manual J, S and D calculations.

ELECTRICAL PLAN:

1. Verify outdoor lighting calculations are correct.



If you have any questions please contact:

Rafael Cancino
(520) 909-4891
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2014 CPIERCE1 OUT TO CUSTOMER Completed
01/06/2014 CPIERCE1 REJECT SHELF Completed