02/20/2014 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 2-25-14
Activity: T14CM07442
Address: 2026 E Poquita Vista
Applicant: TM Building

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

FOUNDATION PLAN:
1. All exterior framed walls require continuous concrete footings min. 12"wide x 12" below grade with treated sill plates and anchor bolts per R403.1 & R403.1.6 (including carport and porch enclosures).

PLUMBING PLAN:
2. If new gas supply piping will be installed, a gas piping diagram will be necessary, G2413.1, Table G2413.4 (1).

MECHANICAL PLAN:
3. Provide a complete mechanical plan for roof mounted gas pack that complies with 2012 IRC and sized in accordance with ACCA Manuals J/D/S.

ELECTRICAL PLAN:
4. Correct all mislabeled electrical code references. As of 1/01/2013 all code references should refer to the currently adopted code or appeal must be made to the Building Official for alternate code use.
5. Justify quantity of outlets specified on circuit number 15.

INTERNATIONAL ENERGY CONSERVATION CODE:
6. Specify the "R" value of the insulation in accordance with N1102.1. Tucson is in climate zone 2B.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review