Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07425
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/09/2013 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 12/09/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 12/09/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/09/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/09/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 12/09/2013 | RONALD BROWN | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 12/12/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 12/12/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 12/12/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/12/2013 | FRODRIG2 | WWM | REVIEW | Completed |