Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T13CM07337
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/02/2014 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Reqs Change | PROVIDE INFORMATION FOR WALL AND CEILING CONSTRUCTION. |
| 01/02/2014 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | FONT SIZE TO BE 3/32" MINIMUM. YOU MAY DELETE THE ELECTRICAL NOTES ON PP DA-1 AS THIS IS THE ONLY PLACE FONT IS NON-COMPLIANT AND THE NOTES ARE EXTRAENEOUS. PREVIOUS CORRECTION COMMENT NOT ADDRESSED. PROVIDE OUTDOOR LIGHTING INFORMATION TO SHOW COMPLIANCE WITH THE CITY OF TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. |
| 12/31/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Verify the scale of the partial plans for the restroom; they are noted as being 1/8": 1'- 0" but it appears to be ΒΌ": 1'- 0". Reference: Section 107.2.1, IBC 2012. 2. Revise the font size used on drawing DA-1 to a minimum of 3/32-inch. Reference: Section 107.2.1, IBC 2012. 3. The water pressure calculations note a maximum pressure of 81 PSI. Provide a water pressure regulator (with a strainer) to reduce the maximum pressure to less than 80 PSI. Reference: Section 604.8, IPC 2012. 4. Clarify which material is to be used for the water distribution piping above grade. The plumbing notes list both Type M copper and "Thermoguard" (PEX?). Reference: Section 605.4, IPC 2012. 5. Verify the minimum flow required to initiate heating for the specified water heater. The specification sheet for the Eemax model EX65T-FS lists 0.5 GPM but the factory installation instructions give a minimum flow as0.6 GPM. The maximum flow for a lavatory is 0.5 GPM. Reference: Section 607.1, IPC 2012. 6. Install a cleanout downstream of the backwater valve for maintenance of the building sewer. Note that the 3" cleanout located in the restroom will be adequate for maintaining the building drain and the building sewer up stream of the backwater valve. Reference: Section 708.3.5, IPC 2012. |
| 12/31/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/31/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide the specifications for the fan/light unit proposed for the restroom. The minimum exhaust flow shall be 70 CFM (intermittent operation). Reference: Section 403.3, IMC 2012. |