Permit Number: T13CM07320
Parcel: 113011790

Address:
3751 N CHERRY AV

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T13CM07320
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/03/2014 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Reqs Change T13CM07320
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, please provide revised plans and calculations, highlighting any changes or with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2012 International Residential Code and 2012 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

GENERAL REQUIREMENTS:

All engineers and architects involved in the design of the structure are to seal the related sheets of plans, details and calculations in accordance with the rules of the State Board of Technical Registration.

The City of Tucson adopted the 2012 IRC with amendments on 1/1/2012. Show the current code reference on the plans.

SITE PLAN:

1. Indicate the location of utility meters and gas, water, electric and sewer lines from property line to building, R106.1.1.

FOUNDATION PLANS:

1. Show or notate an 6" minimum separation of untreated exterior framing above finished grade, R319.1 item 2.
2. Show the required minimum one #4 reinforcement rebar 3" from edge in the footer, R403.1. (City of Tucson Amended).
3. Show the minimum 12" footing depth below undisturbed soil, R403.1 with #4 (top & bottom) continuous reinforcement. The continuous footing requirement applies to all new exterior walls.
4. Locate and specify all anchor-bolt spacing on the foundation plan. Minimum ½" diameter with (anchor bolt length for assuring) 7" embedment into concrete or masonry, R403.1.6. Maximum spacing 6' o/c and within 12" of each sill plate end, R403.1.6.
5. Show all foundation hold-downs for alternate brace wall panels on the Foundation Plan, R403.1.6. Show required hold-down locations for continuously sheathed walls if panels are less than minimum width, Table R602.10.5.
6. Show Alternate Braced Wall Panel device location and installation method for providing the required 1800 LBS uplift capacity, Table R602.10.6.1.

FLOOR PLANS:

1. Provide all window sizes and types, and designate the operable portion of windows, as well as the location of tempered glass (within 18" of the floor or 24" of doorways), R308.4. CoT Amended.
2. Show the door from a garage to dwelling with a 20-minute fire rating (or 1-3/8" solid core) with self-closing and self-latching provision, 2012 Amendment.
3. Locate and identify brace wall lines on the plans, R602.10.1 along with appropriate panel lengths, R602.10.3 for identified method, R602.10.4 and connection schedule, Table R602.10.4.

STRUCTURAL PLANS:

1. In addition to showing compliance with Table R602.10.3(1) for minimum total panel length on each wall line, "qualify" each braced wall panel for: (1) minimum panel length (width dimension), R602.10.5 as limited by Table R602.10.5 based on wall height and size of adjacent wall opening; and (2) one of the five required end conditions Figure R602.10.7 when continuously sheathing the wall line.
2. Locate and identify brace wall panel materials and locations along with the appropriate fastening schedule, Table R602.10.4. The required fasteners vary with the selected panel method that may be different for each wall line.

PLUMBING PLANS:

1. Show a plumbing code recognized by the City of Tucson, 2012 IRC rather than UPC.
2. Show hot water pipe with minimum R-3 insulation, N1103.4.2.
3. Show a pressure and temperature relief valve at the water heater. Note a metallic T&P line terminating at the exterior 6 inches above grade facing down, P2803.6.1.
4. Provide the water pipe diameter between the meter and shut off valve in compliance with P2903.7. A minimum 1" service pipe is required for supplying water to more than 9.5 fixture units.
5. Show a cleanout at the base of each vertical waste or soil stack, P3005.2.
6. Show gas pipe sizes in compliance with connected demand, G2413.3 & Table G2413.4(1). Provide a gas line isometric or table for showing the BTU demand and length of line to each gas appliance.

MECHANICAL PLANS:

1. Provide heating facilities in all habitable rooms, R303.8.
2. Show supply ducts with minimum R-8 insulation (includes vented attics) except when completely located inside the thermal envelope, N1103.2.1. All other ducts require R-6 insulation.
3. Provide an equipment specification list including the (furnace and evaporative cooler) tonnage capacity, M1302.1.
4. Show impact protection for appliances located in the garage, M1307.3.1.
5. Provide Manual J/S/D calculations in accordance with M1401.3, M1601.1. Systems shall be sized in accordance with Manual S based on building loads calculated in accordance with Manual J and duct systems sized in accordance with Manual D.
6. Show dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Show or notate the requirement for a carbon monoxide detector outside of bedroom doors, when the dwelling includes an attached garage or gas appliance, R315.
2. Panelboards may not be located in clothes closets or bathrooms, E3405.4.
3. Show the kitchen island receptacle outlet circuit number, E3404.11 & E3706.2.
4. Show a GFCI receptacle outlet on the same level within 25' of exterior HVAC equipment, E3901.12.
5. Show wall switch controlled lights at the attached garage door, E3903.3.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Both standard and high density R-38 batt insulation requires a space greater than provided with 2" x 8" framing at the Arizona Room. Identify the product that provides the intended value, or provide an appropriate ceiling cavity space.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/06/2014 CPIERCE1 REJECT SHELF Completed