Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07311
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2014 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Section 929 Water cooled refrigeration/heat removal systems—water conservation. A water-cooled refrigerating system, (defined as refrigerating system using water, all, or in part, for condensing a refrigerant), shall not discharge more than three gallons of condenser waste water per nominal ton per hour into an approved sanitary disposal system. Condenser wastewater discharge shall be accomplished by the use of an air gap, as described in the International Plumbing Code. Each water-cooled refrigerating system shall be provided with one or more of the following water-saving devices: (a) a cooling tower: or (b) an evaporative condenser; or (c) an approved water circulating device.[Initial coment: Provide information for the operation of the batch freezer (K8) with regard to its water use. Reference: section 929, IMC 2012, as amended by the City of Tucson.] |
02/24/2014 | CPIERCE1 | WWM | REVIEW | Completed |