Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07311
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/17/2014 | SPOWELL1 | WWM | REVIEW | Needs Review | |
12/13/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/13/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/13/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
12/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
12/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide separate indirect waste pipes for each compartment of the 3-compartment sink to protect against cross-contamination or fouling. Reference: Sections 801.2 and 802.1.8, IPC 2012. 2. Verify that the lack of a grease interceptor is acceptable to the Regional Wastewater reclamation department of Pima County (contact: Rusty Riccaboni 724-6200). 3. Provide information for the operation of the batch freezer (K8) with regard to its water use. Reference: section 929, IMC 2012, as amended by the City of Tucson. |