Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T13CM07262
Parcel: 13809006D

Address:
6255 S 12TH AV

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM07262
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/16/2013 MARTIN BROWN FIRE REVIEW Denied Unable to determine type of appliciances in kitchen. Any cooking device capable of producing grease laden vapors will require a Type 1 Hood, with a fire suppression system contained within. Fire approval contingent upon Mechanical approval.
12/16/2013 LOREN MAKUS ENGINEERING REVIEW Approved
12/16/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM07262
6255 S 12th Av
SDA New Church

1. City of Tucson Submittal Requirements indicate that a calculation showing compliance with the 2012 City of Tucson Outdoor Light Code be provided. Though the parking lot lighting is future, lighting installed on the building is to be considered.
2. City of Tucson Submittal Requirements indicate compliance with the 2012 IECC be provided. On New buildings the Architect must choose which Commercial Compliance Option from 2012 IECC is to be used,(options shown in Section C401), you my be required to comply with ASHRAE or Section C406 tables of the 2012 IECC which would put you over the watts per square foot allowed total. Architect did not provide 2012 IECC calculations or option chosen.
3. Sheet E4.0 --- the MDP Switchboard on one line diagram shows a 1200 amp main overcurrent device, the MDP Panel shows an 800 amp main overcurrent device. The Switchboard should show the other items originating from it such as the AC's and the WH's.
4. Indicate circuit breakers are to be Fully Rated as panels, since no mention of Series Rated Systems made.
2011 NEC 110.9,110.10 and 110.22.
5. Could not locate circuits L1-25, L2-26 and 28.

Ray Majuta
Elect Plan Review
PDSD, Tucson
12/17/2013
Ray.Majuta@tucsonaz.gov
12/17/2013 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Esperanza SDA Church
T13CM07262
Building Plan (1st Review)

TRANSMITTAL DATE: December 17, 2013

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning has reviewed the building plans and it appears that they meet the requirements of the development package. Once all other PDSD review agencies have approved the building plan Zoning will approve the plan.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/18/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Reqs Change SHEET A2
1. Provide a Hi/Low water dispenser as per the 2012 IBC, Section 1109.5 and 2009 ICC A117.1, Section 602.
2. Provide a large scale detail of the ramp located in the north west corner of the Sanctuary showing all accessibility requirements such as dimensions, widths, lengths, slopes, grade elevations, handrails, landings, and connection to accessible routes.
3. Make the route to the baptismal tub accessible.
4. Make both bath toilets accessible.
5. The women's gathering/changing area is not accessible. Provide a ramp similar to the men's access.
6. Show the sanctuary accessible seating details and arrangement.
7. Provide a large scale Men's/Women's toilet rooms showing all accessible requirements such as dimensions, clearances, fixtures, accessories, wall finishes and signage.
8. Provide one 3'-0" wide urinal stall.
9. Provide a range hood exhaust along with all structural details and calculations.
10. Provide wall make up and finishes where range is located.
SHEET A-4
11. The ramp handrails are non-compliant with 2012 IBC, Section 1010 and ICC A117.1, Section 405.8.
a. The handrails shown also do not comply with detail 13/D1.
SHEET A-5
12. Provide structural details and calculations for all roof top mounted HVAC equipment.
SHEET A-6
13. At door schedule note 2: Substitute "2012 IBC Chapter 11 and 2009 ICC A117.1" for "ADA".
SHEET D-1
14. At detail 18: Delete all door mounted signage.
15. At details 7 and 8: Provide wall finish as required by the 2012 IBC, Section 1210.
16. Provide Hi/Low water dispenser.
SHEET P1.1
17. Provide structural details and calculations for all suspended or wall mounted water heaters.
SHEETS A.5, E2.1 and M1
18. Between the roof plan, the mechanical plan and the electrical plan, there are three different types of mechanical air conditioning systems. Please reconcile.
SHEET S-1
19. Provide a lintel schedule.
20. Provide additional framing details needed to explain the project.

ADDITIONAL STRUCTURAL COMMENTS FROM ERIC NEWCOMB
1. SHEET S-1: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE SHEARWALL NOTES AND THE SHEARWALL NOTATIONS/CONSTRUCTION.
2. SHEET S-1; ROOF FRAMING PLAN: ADD A LINTEL SCHEDULE TO THE PLAN, OR ADD NOTES FOR TYPICAL LINTELS. PROVIDE CALCULATIONS FOR THOSE LINTELS.
3. SHEET S-2; DETAILS 5, 6, AND 7: DOES THE 8" X 8" COLUMN BASE PLATE ALLOW ENOUGH EDGE CLEARANCE WITH A 4" SQUARE TUBE COLUMN? INCLUDE A DETAIL ON THE DRAWINGS.
4. STRUCTURAL SHEETS: ADD STRUCTURAL GENERAL NOTES, INCLUDING DESIGN LOADS, DESIGN CODES, SOILS, CONCRETE, REINFORCING, WOOD, GLULAM, WELDING, BOLTS (IN WOOD), BOLTS (ANCHOR), CONNECTORS, AND TRUSSES.
5. STRUCTURAL CALCULATIONS; PAGE 5: THE LATERAL ANALYSIS INDICATES THE 2006 IBC WAS USED. REVISE THIS TO THE 2012 IBC, AND VERIFY THE CALCULATIONS USING THE 2012 IBC. INCLUDE REVISED CALCULATIONS.
6. STRUCTURAL CALCULATIONS (PAGES 7 AND 9); SHEETS S-1 AND S-2: WHERE ON THE DRAWINGS DOES THE NAILING OF THE ROOF PLYWOOD PER THE CALCULATIONS SHOW UP? VERIFY.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
END OF REVIEW
12/20/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Completed
12/26/2013 ROBERT SHERRY WATER REVIEW Approved
12/27/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide energy code compliance calculations for the building envelope; use the climate zone for Tucson. Provide sufficient detail on the drawings to evaluate the energy compliance of the building envelope. The information shall, as a minimum, include U-factors of the envelope systems and fenestration components, along with the R-values of the insulation and the SHGC for the fenestration. Reference: Sections C103.2 and C401.2, International Energy Conservation Code 2012.
2. Show that the proposed HVAC system meets the requirements of Sections C403.2, C403.3 and, if neither the efficient lighting system nor the on-site renewable energy options are selected, C406.2, IECC 2012 (e.g. provide the mechanical energy code compliance certification from COMcheck). Reference: Section C303.1, International Energy Conservation Code 2012.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C403.2.1 and C403.2.2, IECC 2012.
4. The mechanical plan indicates the proposed location of the rooftop condensing units but the fan coil units are not shown on the mechanical plan. Reference: Section 107.2.1, IBC 2012.
5. Coordinate the mechanical plans with the electrical plans. The mechanical plans show nine split systems (actually only 7 ½ systems - the condensing unit for AC-8 is missing) and four exhaust fans but the electrical drawings show three packaged rooftop units and two exhaust fans. Reference: Section 107.2.1, IBC 2012.
6. Provide structural calculations to verify that the proposed roof is capable of supporting the point loads due to the installation of the roof top units. Reference: Section 302.1, IMC 2012.
7. Provide structural details to show how the fan coil units are to be connected to the building structure. Reference: Section 302.1, IMC 2012.
8. Show that the equipment is being installed in accordance with the conditions of its listing and the manufacturer's installation requirements (e.g. maximum supply air delivery, maximum allowable outside air when operating at high ambient temperatures, etc.). Reference: Section 304.1, IMC 2012.
9. Show the size, routing, and termination of the condensate drains from the fan coil units and for the ductless split system. Reference: Section 307.2.1, IMC 2012 as amended by the City of Tucson.
10. Provide auxiliary drain pans or secondary drain systems for the fan coil units. Reference: Section 307.2.3 IMC 2012.
11. Show how ventilation will be provided for the occupied spaces, 110 and 119. Reference: Section 401.2, IMC 2012.
12. Provide calculations demonstrating adequate ventilation using the current code (i.e. ASHRAE 62.1 was not adopted by the City of Tucson and is not part of the 2012 IMC). Reference: Section 403.2, IMC 2012.
13. Ventilation calculations for HVAC systems supplying multiple zones shall take into account the different occupancy loads in each zone. Reference: Section 403.3.2.3, IMC 2012.
14. Show how outside (ventilation) air is being supplied to the fan coil units and for the ductless split system. Reference: Section 107.2.1, IBC 2012.
15. Provide specifications for the restroom exhaust fans in rooms 107 and 109 and show the location of the termination of these exhaust fans with respect to any outside air intakes. Reference: Section 501.3.1, IMC 2012 and Section 107.2.1, IBC 2012.
16. Provide specifications for the restroom exhaust fans in rooms 117 and 118 and show the location of the termination of these exhaust fans with respect to any outside air intakes. If these fans are operating intermittently (e.g. with the lights), the minimum exhaust air flow is 70 CFM per water closet. Note that no power is shown for these fans on the electrical drawings. Reference: Section 501.3.1, IMC 2012 and Section 107.2.1, IBC 2012.
17. Provide a design for the "stove hood VTR". Reference: Section 501.3.1, IMC 2012 and Section 107.2.1, IBC 2012.
18. Clarify the nature of the "warming kitchen" with respect to the frequency of operation, the quantity of food being prepared, and the appliances to be used for food preparation. Reference: Section 507.1, 507.2, 507.2.1, and 507.2.2, IMC 2012.
19. Revise the mechanical design as required to avoid using the corridor as a return air duct (see AC-1). Reference: Section 601.2, IMC 2012.
12/27/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. The 2012 International Plumbing Code has been adopted by the City of Tucson. The use of the 2012 Uniform Plumbing Code is allowed provided an appeal to the building official is filed (there is no charge for this appeal). This review has been done using the 2012 UPC.
2. Provide the number of drinking fountains that complies with the requirements of Section 1109.5.1, IBC 2012.
3. Provide the design details and any listing information for the installation of the baptistery. Reference: Section 407.1, UPC 2012.
4. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 421.2, UPC 2012 and Section C404.3, IECC 2012.
5. Show that the restroom floors slope toward the floor drains. Reference: Section 418.5, UPC 2012.
6. The minimum residual water pressure is 15 PSI unless it can be shown that no specified fixtures or appliances require minimum residual pressures greater than 15 PSI. Note that the specified flushometer water closets require a minimum residual pressure of 20 PSI. Reference: Section 608.1, UPC 2012.
7. Clarify and coordinate the specified water heaters shown on the plumbing plan, water piping diagram, and the plumbing specifications. Reference: Section 103.2.2, UPC 2012.
8. Provide a detail of each water heater installation, including the excess pressure relief, expansion tank, vacuum relief, recirculating pump and valves. Reference: Sections 103.2.2, 606.2, 608.3, 608.4, 608.5, and 608.7 UPC 2012.
9. Specify the piping material to be used for water service to the building, water heater connections, and drains for relief valves. Reference: Sections 604.0 and 608.5, UPC 2012.
10. If the minimum water pressure from Tucson Water is 78 PSI, show how the water pressure will be limited to less than 80 PSI. Note that the installation of a pressure regulator may affect the pipe sizing calculations. Reference: Section 608.2, UPC 2012.
11. Revise the water pressure calculations to include the pressure drop due to the reduced pressure backflow preventer as determined by the manufacturer of the valve assembly. Reference: Section 610.2, UPC 2012.
12. Clarify how the water supply pipe sizes were determined; the calculations presented appear to be from a mixture of UPC and IPC methods and tables. Verify that the maximum water velocities and pressure drops for the PEX tubing are considered in the calculations. Reference: sections 103.2.2 and 610.1, UPC 2012.
13. Revise the schedule of waste fixture units for all plumbing fixtures using the values shown in table 702.1, UPC 2012. The installation is for assembly use. Show how the number of drainage fixture units for the baptistery was determined. Reference: Section 702.1, UPC 2012.
14. Provide a vent for each fixture trap (e.g. the floor drains). Reference: Sections 901.0 and 910.1, UPC 2012.
15. Provide the listing information for the weather caps specified for the plumbing vents. Vent pipe openings shall not be reduced in size as they extend towards their termination. Reference: Section 905.4, UPC 2012.
16. Revise the size of the vertical wet vent serving the water closet and the urinal. The size of a wet vent shall be a minimum of one pipe size greater than that required for the drain of the upper fixture (the minimum drain size for a urinal is 2"). Reference: Section 908.1.1, UPC 2012.
17. Provide roof drainage calculations and plans. Provide overflow protection for the roof. Reference: Section 1101.11, UPC 2012.
18. Provide the dimensions for the roof scuppers and downspouts. Reference: Sections 1101.11 and 1106, UPC 2012.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/30/2013 SHANAE POWELL APPROVAL SHELF Completed