Review Date Reviewer's Name Type of Review Description Status Comments
12/02/2013 KEN BROUILLETTE FIRE REVIEW Approved
12/02/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom fans so that all of the air supplied to each restroom is exhausted during occupied hours.
12/02/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/02/2013 ROBERT SHERRY WATER REVIEW Approved
12/02/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/02/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a vacuum relief valve for the water heater.
2. Provide an ASSE 1070-listed mixing valve for the lavatories, set for a maximum of 110 degrees Fahrenheit.
12/02/2013 RONALD BROWN COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
12/03/2013 SPOWELL1 WWM REVIEW Needs Review
12/03/2013 MICHAEL ST. PAUL ZONING REVIEW Approved
12/03/2013 LAITH ALSHAMI ENGINEERING REVIEW Approved