| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/02/2013 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 12/02/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom fans so that all of the air supplied to each restroom is exhausted during occupied hours. |
| 12/02/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 12/02/2013 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 12/02/2013 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 12/02/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a vacuum relief valve for the water heater. 2. Provide an ASSE 1070-listed mixing valve for the lavatories, set for a maximum of 110 degrees Fahrenheit. |