Permit Number: T13CM07181
Parcel: 132130280

Address:
1515 E AJO WY

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T13CM07181
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/03/2013 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET C1.0; SCHEDULE OF DRAWINGS: THE SCHEDULE INDICATES A SHEET C1.1, WHILE THE DRAWING IS NOTED AS SHEET C1.2. CLARIFY.
2. SHEET A2.1; LOADING DOCK BASIN PLAN 2: THE PLAN SHOWS A SECTION 4/A2.1 CUT AT THE SUMP PIT, WHILE THE SECTION IS SHOWN AS 3. CLARIFY.
3. STRUCTURAL CALCULATIONS; SHEET 1 (SOIL): THE CALCULATIONS INDICATE A SOIL REPORT WAS USED FOR THE FOUNDATION DESIGN. PROVIDE THAT REPORT FOR REVIEW.
4. STRUCTURAL CALCULATIONS; PAGE 14: WHERE DOES THIS CONCRETE BASEMENT WALL DESIGN OCCUR ON THE PLAN? VERIFY.
5. STRUCTURAL CALCULATIONS; PAGE 14: THE CONCRETE DESIGN STRENGTH SPECIFIED IN THIS CALCULATION IS 3000 PSI, ALTHOUGH THE STRUCTURAL GENERAL NOTES INDICATE 2500 PSI. CLARIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/06/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/16/2013 ROBERT SHERRY WATER REVIEW Approved
12/16/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Install the underground duct with a minimum slope of 1/8" per foot to allow drainage to a point of access. Reference: Section 603.8.1, IMC 2012.
12/16/2013 LOREN MAKUS ENGINEERING REVIEW Denied The development package must be approved before the building plan may be approved.
12/16/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Revise the size of the combination drain and vent pipe to correspond to the requirements of Table 915.3, IPC 2012 (a 2" pipe can accommodate no more than 4 drainage fixture units).
12/16/2013 DAVID RIVERA ZONING REVIEW Reqs Change FROM: PDSD Zoning Review Section
David Rivera
Principal Planner

PROJECT: T13CM07181
1515 E Ajo Way
Foundation Plan approval only

TRANSMITTAL DATE: December 16, 2013

DUE DATE: December 27, 2013

COMMENTS:

01. Zoning has reviewed the plans for the foundation only and while they are in substantial compliance with the development package site plan submitted for review, zoning cannot approve the foundation plan until the development package is approved.

Once the development package site and grading plan is approved zoning can approve the foundation plan.

If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/03/2014 SHANAE POWELL OUT TO CUSTOMER Completed
01/03/2014 CPIERCE1 REJECT SHELF Completed