Permit Number: T13CM07180
Parcel: 11711001C

Address:
60 W ALAMEDA ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T13CM07180
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2013 DAVID RIVERA ZONING REVIEW Approved
11/27/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
11/27/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T13CM07180
60 W Alamedia St

1. Provide a detail on Sheet E2.1 showing compliance with 2011 NEC, 300.19, Supporting conductors in vertical raceways. Supports required not greater than 40' for conductors over 500 kcmil through 750 kcmil.

Ray T Majuta
Electrical Plan Review
PDSD, Tucson
11/27/2013
Ray.Majuta@tucsonaz.gov
11/27/2013 LHANLY1 WATER REVIEW Approved
11/27/2013 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Passed
11/27/2013 LHANLY1 WWM REVIEW Passed
11/27/2013 LEERAY HANLY PLUMBING-COMMERCIAL REVIEW Passed
11/27/2013 JASON GREEN ENGINEERING REVIEW Approved
11/27/2013 MARTIN BROWN FIRE REVIEW Approved
11/27/2013 LHANLY1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed