Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T13CM07180
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/27/2013 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/27/2013 | LEERAY HANLY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/27/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T13CM07180 60 W Alamedia St 1. Provide a detail on Sheet E2.1 showing compliance with 2011 NEC, 300.19, Supporting conductors in vertical raceways. Supports required not greater than 40' for conductors over 500 kcmil through 750 kcmil. Ray T Majuta Electrical Plan Review PDSD, Tucson 11/27/2013 Ray.Majuta@tucsonaz.gov |
| 11/27/2013 | LHANLY1 | WATER | REVIEW | Approved | |
| 11/27/2013 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Passed | |
| 11/27/2013 | LHANLY1 | WWM | REVIEW | Passed | |
| 11/27/2013 | LEERAY HANLY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 11/27/2013 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/27/2013 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/27/2013 | LHANLY1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |